Ecoplast
home page mail to Ecoplast
site map русская версияenglish version
Home About News Catalog Support Dilers Contacts FAQ
Pipes for cables and wiring installation
Minitrunking MEX / ECO
Cable trunking system INSTA
Slotted ducts
Aluminum mini-columns
PVC Corrugated flexible pipes
HDPE corrugated flexible pipes
PP corrugated flexible pipes
PVC pipes reinforced
Halogen Free corrugated
Smooth rigid PVC pipes
HDPE rigid smooth pipes, single-wall
HDPE double-wall pipes
Accessories for all plastic pipes
Boxes and fittings
Connectors quick-terminal
Service floor boxes LUK
LAN components
Wiring devices
Steel Cable Trays
Plastic systems for air-conditions and water supply
Industrial plugs and sockets
Objects with the products Ecoplast
Catalogs
Certificates
HDPE corrugated pipe

Corrugated pipes (corrugated) of the HDPE - cable support system for the professional / concealed wiring in the walls (the walls), ceilings (the ceiling), floor of residential, office and industrial premises.

The system consists of corrugated plastic pipes of different diameters, and internal and external distribution boxes and shields. The purpose of corrugated pipe with accessories - providing a reliable set of wiring with a guaranteed savings of labor costs and installation time

Material - composition of the HDPE - is an environmentally safe material and does not contain any harmful substances, wide operating temperature range from -25°C to 90°C allows for electrical work in both hot and cold conditions with no loss of mechanical and insulation properties.

Corrugated pipe manufactured in two versions: with a probe for pulling cable or probe.

Products are certified in accordance with:
   - System Certification GOST-R State Standard of Russia,
   - Certification System of the State Sanitary-Epidemiological Service of the Russian Federation

Flexible corrugated pipe is heavy. BH Series
composition of the HDPE, IP 55, color - black RAL 9005
Material:
composition of HDPE
Standard:
GOST 50827-95 (IEC 670-89)
Degree of protection:
IP 55 according to GOST 14254 (IEC 529)
Mounting conditions:
for open / concealed wiring in walls, in ceilings of noncombustible materials
Low installation:
-25°С to +90°С
Durability:
more than 750N on 5 cm at 20°C (heavy duty)
Color:
black RAL 9005, at the request of: yellow, gray, white, blue, orange (minimum order - 5000 m of the same color)
Dielectric strength:
not less than 2000 V (50 Hz for 15 min)
Insulation resistance:
not less than 100 MW (500 V for 1 min)
Equipment
Code Outer diameter (D), mm The inside diameter (d), mm Unit The number in the bay, m The presence of the probe
21016 16 10,7 м 100 -
21020 20 14,1 м 100 -
21025 25 18,3 м 50 -
21032 32 24,3 м 25 -
21040 40 31,2 м 20 -
21050 50 39,6 м 15 -
21116 16 10,7 м 100 +
21120 20 14,1 м 100 +
21125 25 18,3 м 50 +
21132 32 24,3 м 25 +
21140 40 31,2 м 20 +
21150 50 39,6 м 15 +